Valid HTML 4.01 TransitionalValid CSS!Viewable With Any Browser !
accpower al enerji elektrik  
 
Circuit Breakers and Disconnectors

Sectionalizer

General Features

It is a switching component that can close, carry and cut all currents up to rated normal current and can carry the short-circuit currents for a while. It can close on the rated short-circuit current at least 5 times. Also, it provides the desired level of insulation for disconnectors at the open position. It can be controlled with remote or command as mechanical and electrical.



Technical Features

Rated voltage

36kV

17.5kV

12kV

7.2kV

Lightning impulse voltage

170kV

95kV

75kV

60kV

Power frequency impulse voltage

70kV

38kV

28kV

20kV

Rated frequency

50Hz

Rated current

630A

Rated short-circuit current

12.5kA

Rated short-circuit closing current

2.5 x rated short-circuit current

Short-circuit time

1sec

The number of poles first opened

1.5

Temporary recovery voltage

IEC 60265

Opening time

<1sec

Closing time

<5sec

Closing number on rated short-circuit current

At least 5 times

Electrical withstand

At least  100 times on-off on the rated current

Mechanical withstand

Idle at least 5000 times on-off



 

 
web tasarım